Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T99CM02114

Parcel: 113042800


Addresses:

919 E HALCYON RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/22/2000 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
09/20/2000 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/1. K. SINK VENT CANNOT 90 HORIZONTAL BELOW 6" ABOVE SINK FLOOD RIM. 2. A/C CONDENSATE RUBBER CONNECTION NOT ALLOWED IN WALL. 3. FIRE BLOCK BATHROOM DROP CEILING AT CLOSES. 4. NAIL PROTECT N. BATH LAV. WASTE AT FLOOR PLATE. 5. HEADERS MUST BEAR ON TRIMMERS. 6. LAUNDRY WASTE MUST BE 2" IN DIAMETER AND HAVE VENT AND TRAP. 7. LAUNDRY SINK 1 1/2 DRAIN TRAP ARM EXCEEDS 42" TO VENT. 8. 2 A/B REQUIRED IN EACH SILL PLATA. 9. ALL OUTSIDE ELECTRIC WIRES. 10. CARPORT LEDGER NOT PROPERLY ANCHORED.
08/15/2000 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/1. REVISE PLAN FOR RELOCATION OF WATER HEATER AND FOR CHANGE FROM BATH TUBS TO SHOWERS. 2. REVISE PLAN FOR REVISED MECHANICAL SYSTEM FROM ROOF MOUNTED HEAT PUMP UNIT TO GROUND AND INTERIOR SPLIT UNIT AND DUCT WORK. 3. NONE OF ELECTRIC IS PER PLAN. EITHER BUILD TO PLAN OR REVISE PLAN TO AS BUILT.
07/19/2000 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0925*/NO PLANS ON SITE.