Permit: T99CM02026

Parcel: 11105010B

Inspection Status: Correction Required

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
03/10/2000 PLUMBING - INTERMEDIATE Correction Required ADDTL COMMS - 1. WASTE AND VENT SYSTEM OK 2. OVERHEAD WATER DISTRIBUTION OK 3. GAS PRESSURE TEST OK 4. REVISED AND APPROVED DRAWING FOR GAS LINE AND WASTE AND VENT SYSTEM OK 5. ALL CORRECTIONS HAVE BEEN MADE 6. OK TO DRYWALL
03/06/2000 PLUMBING - INTERMEDIATE Correction Required ADDTL COMMS - 1. REVENT OVERLOAD OF FIXTURE UNITS @ ABOVE CEILING REVENT @ RM #13 &10 VTR MUST BE 3 2. SECOND GAS LINE NOT SHOWN ON PLAN? 3/4 GAS LINE 3. NO CLOSET RINGS INSTALLED.
03/06/2000 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0000*