Inspection Status: Correction Required
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/24/1999 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - 1. SECURE GROUNDING ELECTRODE CONDUCTOR TO MASONRY (TIE-WRAPS NOT ACCEPTABLE FOR ATTACHING 3/0) 2. GROUND CONTRACTOR CABINET AND TIME CLOCK AND TIGHTEN 2 LOCKNUTS AT CABINET. 3. INSTALL MISSING BASE COVERS AND HANDHOLE COVERS ON ALL EXISTING POLES 4. SEAL UNUSED OPENING BELOW WEST CONTACTOR PANEL 5. PER T.F.D. AND C.O.T. PLEASE HAVE OWNERS REP, LABEL ALL ADDRESSES PER T.E.P. SPECIFICATION. |
| 11/24/1999 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |
| 11/16/1999 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |