Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/23/2001 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/16/2001 |
BUILDING - FINAL |
|
Denied |
1) POST ADDRESS ON STRUCTURE |
| 09/25/2001 |
BUILDING - FINAL |
|
Denied |
1) PROVIDE DOUBLE WALL FLUE AT WATER HEATER 2) BLOCK CONDENSATION LINE AT ROOF 3) WILL REFEE FOR NEXT INSPECTION |
| 08/17/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) CONDENSTATION LINE NOT INSTALLED CORRECT, PROVIDE VENT PIPE AFTER P TRAP DRAIN INTO VTR WITH SAN T BUSHING 2) INSTALL DOUBLE WALL FLUE PIPE AT HOT WATER OR PROVIDE 6" CLEARANCE FROM COMBUSTIBLE MATERIAL |
| 04/12/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/COMBUSTION RELIEF FOR HOT WATER NOT INSTALLED CORRECT AND NOT SIZED ACCORDING TO PLAN, IDENTIFY ALL CIRCUIT BREAKERS AT PANEL, POINT ABS ON ROOF,SEAL PENETRATIONS AT DOOR AND SLIDER FROM INFILTRATION, PROVIDE CLEAN OUT FOR WASHER/KITCHEN CLEAN OUT NEEDS TO BE ACCESSIBLE, ADJUST BOMBER DOOR TO SELF CLOSE INSTALL HINGES, PROVIDE BOND WIRES FOR GAS/WATER PIPES, REMOVE OUTLETS UNDER COUNTER TOP PROVIDE PROTECTIVE COVER, PROVIDE 221/2" X 30" ATTIC ACCESS |