Permit: T99CM01511

Parcel: 116193700

Inspection Status: Correction Required

Inspection History: ELECTRIC - TEMPORARY SERVICE

Permit Number - T99CM01511

Inspection Description - ELECTRIC - TEMPORARY SERVICE

Inspection Status - Correction Required

Date Description Inspector Results Comments
02/01/2000 ELECTRIC - TEMPORARY SERVICE Correction Required ADDTL COMMS - GFI TEST OK TORGUE OK INSPECTION ON ELECT RM OK NEED APPEAL TO BE APPROVED 1. MAIN OK NEED LETTER ON GFI TEST AND TORGUE 2. APPEAL NEEDS TO BE APPROVED 3. 150 KVA TRANS SCRAP PAINT OFF BOTTOM GROUND LUGS THEN OK TO CLOSE
02/01/2000 ELECTRIC - TEMPORARY SERVICE Denied DUCT ABOVE SWGEAR IN VIO
02/01/2000 ELECTRIC - TEMPORARY SERVICE Denied OF NEC 384-4
02/01/2000 ELECTRIC - TEMPORARY SERVICE Denied LETTER ON SWGEAR TORQUE
02/01/2000 ELECTRIC - TEMPORARY SERVICE Denied AND ON SWGEAR GFI TEST
02/01/2000 ELECTRIC - TEMPORARY SERVICE Denied SUBMITTED AND APPROVED
01/27/2000 ELECTRIC - TEMPORARY SERVICE Correction Required ADDTL COMMS - 1. PROVIDE LETTER ON PERFORMANCE TEST ON GFI EQUIP 96 NEC 230-C 2. PROVIDE LETTER ON TORGING FROM WILSON ELECT 3. SET UP FOR TESTING OR TEMP POWER 4. 96 NCEC 384 (1) VIOLATED.
01/27/2000 ELECTRIC - TEMPORARY SERVICE Denied DENIED
07/28/1999 ELECTRIC - TEMPORARY SERVICE Partial Approval PARTIAL APPROVAL