Inspection History Details
Inspection Status: Correction Required
Inspection History: ELECTRIC - TEMPORARY SERVICE
Permit Number - T99CM01511
Inspection Description - ELECTRIC - TEMPORARY SERVICE
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/01/2000 | ELECTRIC - TEMPORARY SERVICE | Correction Required | ADDTL COMMS - GFI TEST OK TORGUE OK INSPECTION ON ELECT RM OK NEED APPEAL TO BE APPROVED 1. MAIN OK NEED LETTER ON GFI TEST AND TORGUE 2. APPEAL NEEDS TO BE APPROVED 3. 150 KVA TRANS SCRAP PAINT OFF BOTTOM GROUND LUGS THEN OK TO CLOSE | |
02/01/2000 | ELECTRIC - TEMPORARY SERVICE | Denied | DUCT ABOVE SWGEAR IN VIO | |
02/01/2000 | ELECTRIC - TEMPORARY SERVICE | Denied | OF NEC 384-4 | |
02/01/2000 | ELECTRIC - TEMPORARY SERVICE | Denied | LETTER ON SWGEAR TORQUE | |
02/01/2000 | ELECTRIC - TEMPORARY SERVICE | Denied | AND ON SWGEAR GFI TEST | |
02/01/2000 | ELECTRIC - TEMPORARY SERVICE | Denied | SUBMITTED AND APPROVED | |
01/27/2000 | ELECTRIC - TEMPORARY SERVICE | Correction Required | ADDTL COMMS - 1. PROVIDE LETTER ON PERFORMANCE TEST ON GFI EQUIP 96 NEC 230-C 2. PROVIDE LETTER ON TORGING FROM WILSON ELECT 3. SET UP FOR TESTING OR TEMP POWER 4. 96 NCEC 384 (1) VIOLATED. | |
01/27/2000 | ELECTRIC - TEMPORARY SERVICE | Denied | DENIED | |
07/28/1999 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | PARTIAL APPROVAL |