Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2000 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
| 10/18/2000 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* FLEX GAS LINES AT FURN. AS USED SERIES #20 AS PER TAG ON LINES RATED 3/8" GOOD FOR 85,000 BTU FRNACES ARE RATED 115,000 BUT INPUT NEED TO HAVE A 1/2" X12" FOR CORRECT LINE SEE TABLE 3-D-2 UMC 1994 FOR CORRECT SIZING CORRECT/RECALL |
|
| 10/13/2000 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* |