Permit: T99CM01472

Parcel: 137322640


Addresses:

5481 S WEMBLY RD

Inspection Status: Correction Required

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
08/20/1999 EXT METAL CLIPS/EXT SHEATHING Correction Required ADDTL COMMS - CORRECT OK
08/19/1999 EXT METAL CLIPS/EXT SHEATHING Correction Required ADDTL COMMS - CLIP POST TO PLATE CHECK ALL. NAIL ALL SHEAR BLOCKING THRU ROOF SHEATHING PER DETAIL 4 & 5 DTI. STOPPED INSP.
08/19/1999 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*
08/17/1999 EXT METAL CLIPS/EXT SHEATHING Correction Required ADDTL COMMS - FRONT ENTRY COLUMN REQUIRES MIN 2 BOLTS PER PLATE AT ANY STRUCTURAL CONNECTION - BOTH SIDES AT ENTRY - 2 SIDES AT COLUMN. SHEARING ALL FOUR SIDES MAY BE AN ALTERNATE OPTION. MISSING CLIPS AT SOLE PLATES AST ENTRY. THANK YOU FOR THE LETTER ADDRESSING A34S IN LIEU OF L90S-HOWEVER, THIS MUST BE APPROVED BY THE COT AND THEN A COPY KEPT WIOTH EACH MODEL LISTED AT ALL TIMES
08/17/1999 EXT METAL CLIPS/EXT SHEATHING Denied DENIED
08/16/1999 EXT METAL CLIPS/EXT SHEATHING Correction Required ADDTL COMMS - PAADS NOT NAILED. PAADS CALL FOR DOUBLE STUDS. PLANS CALL FOR L90S AT LEDGERS (NOT A35). BAY WINDOW NOT CLIPPED/STRAPPED. A35S NOT NAILED UP AROUND HOUSE
08/16/1999 EXT METAL CLIPS/EXT SHEATHING Denied DENIED