Inspection Status: Partial Approval
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/22/2000 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 03/20/2000 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - FOLLOW INST OF FIX BOX OR ADD /SCREW LOCK END OK TO COVER 1ST FLOOR ONLY CALL BACK FOR RECK ON TUES |
| 03/20/2000 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 03/16/2000 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - NEED TO HAVE TABS OR SCREWS AT FIXTURE ENDS. HAVE BOTH ENDS WITHOUT CEILING TILE TO MAKE INSPECTION EASIER. MAKE SURE SEISMIC TIER ARE ALL IN PLACE DIAGONALLY MINIMUM |
| 03/16/2000 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 03/08/2000 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
OK TEC ELEV RM |
| 03/03/2000 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - NEED TO INSTALL J FUSES 175 A |
| 03/03/2000 |
ELECTRIC - INTERMEDIATE |
|
Denied |
ELEV ROOM TEC NOT READY |
| 02/29/2000 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - BATHROOMS OK ROUGH 2. FIRE RISES CLOSET OK |
| 02/29/2000 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
BATHROOMS,FIRE CLOSET OK |
| 02/18/2000 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 02/17/2000 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - IN 1ST FLOOR HALL AND SPKLR CLOSET OK ECO &TS PANEL A W / GFCI ONLY |
| 02/17/2000 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 02/02/2000 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 2ND FLOOR WEST EXCEPT BATH AND CORRIDO 1 ST N WEST OK |
| 02/02/2000 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 01/28/2000 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - CHECK FOR 3/4 KOS OPEN 3XI CHECK CABLE TIER CLOSE TO EDGE OF STUD CAN GET HIT W/SCREW NEED 1 1/4 CLERANCE |
| 01/28/2000 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
PARTIAL APPROVAL |
| 01/14/2000 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - EAST WING OK TO COVER WALLS SUPPORT CONDUIT IN COLUMNS KITCHEN ARE WEST WING OK ROUGH BATHROOMS OK |
| 01/14/2000 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
PARTIAL APPROVAL |
| 10/27/1999 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. OK TO CLEAR TEMP SVC 2. REJECTED UFER NOT READY OR INSTALLED ON BLDG |
| 10/27/1999 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
PARTIAL APPROVAL |