Inspection Status: Denied
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/16/1999 |
FRAMING |
|
Denied |
DENIED |
| 08/26/1999 |
FRAMING |
|
Correction Required |
ADDTL COMMS - 1. ITEMS 4,7,8,9, AND 11 FROM 8/19/1999 OPEN. 2. NAIL PROTECT ALL ELECTRIC. 3. SUPPORT ALL OVER BOARED BEARING STUDS. 4. TWO STUDS NOTCHED GREATER THAN 25% BY KITCHEN-SISTER. 5. MTT28 3 HOLD DOWNS NOT INSTALLED. 6. MID SPAN BLOCK ALL REQUIRED SHEAR WALLS. 7. DOUBLE 2X POST GIRDER TRUSSES. 8. #8 SHEAR NOOK. |
| 08/26/1999 |
FRAMING |
|
Denied |
DENIED |
| 08/19/1999 |
FRAMING |
|
Denied |
IVRS - Inspection 0999* |
| 08/09/1999 |
FRAMING |
|
Correction Required |
ADDTL COMMS - 1. BLOCK GAS PIPE AT RISER UNDER ELBOWS. 2. BEARING STUDS OVER BORED IN MASTER BATH NEED TO DOUBLE THEM. 3. CLIP EACH SIDE OF DOUBLE GIRDERS AND ALL TRUSSES. 4. PLAN CALLS FOR TJI. LPI USED NEED ENG SPANS FOR COMPARING. 5. TRUSSES BEARING ON NON BEARING WALLS NEED 1/2 CLERANCE. 6. NEED FULL SET OF APPROVED PLANS WITH DETAILS CITY OF TUCSON STAMP. |
| 08/09/1999 |
FRAMING |
|
Denied |
IVRS - Inspection 0999* |
| 08/03/1999 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 08/03/1999 |
FRAMING |
|
Not ready for Inspection |
NOT READY FOR INSPECTION |