Inspection Status: Correction Required
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/20/2000 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - OK FOR TEMP POWER FUEL AND TESTING ON FINAL WILL NEED ALL MISCELLANEOUS ITEM EG. COMPLETE RECEPTALES, LIGHT, INSTALL GROUNDING BUSHINGS AND BOND. JUMPER ON 1ST 3 DISCONNECTS FROM MAIN GUTTER FINISH AND COMPLETE ALL JUNCTION BOXER |
| 06/16/2000 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. MYERS HUB CROOKED, LOOSE FITTINGS SERVICE BONDING NOT EFFECTIVE, INSTALL GROUND. BUSH AND BOND JUMPER AT MAIN DISCONNECT 2. FITTING AT TOP OF MAIN DISCONNECT CROOKED. THERE BONDING IS NOT EFFECTIVE. INSTALL A GROUNDING BUSHING AND BONDING JUMPER AT JUNCTION BOX ABOVE MAIN SPECIAL BONDING FOR OVER 250V TO GROUND INTERIOR LOCKED CORRECT AND RECALL |
| 06/16/2000 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* |
| 04/07/2000 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |