Permit: T99CM01125

Parcel: 119310100


Addresses:

2903 W 36TH ST

Inspection Status: Correction Required

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/20/2000 ELECTRIC - INTERMEDIATE Correction Required ADDTL COMMS - OK FOR TEMP POWER FUEL AND TESTING ON FINAL WILL NEED ALL MISCELLANEOUS ITEM EG. COMPLETE RECEPTALES, LIGHT, INSTALL GROUNDING BUSHINGS AND BOND. JUMPER ON 1ST 3 DISCONNECTS FROM MAIN GUTTER FINISH AND COMPLETE ALL JUNCTION BOXER
06/16/2000 ELECTRIC - INTERMEDIATE Correction Required ADDTL COMMS - 1. MYERS HUB CROOKED, LOOSE FITTINGS SERVICE BONDING NOT EFFECTIVE, INSTALL GROUND. BUSH AND BOND JUMPER AT MAIN DISCONNECT 2. FITTING AT TOP OF MAIN DISCONNECT CROOKED. THERE BONDING IS NOT EFFECTIVE. INSTALL A GROUNDING BUSHING AND BONDING JUMPER AT JUNCTION BOX ABOVE MAIN SPECIAL BONDING FOR OVER 250V TO GROUND INTERIOR LOCKED CORRECT AND RECALL
06/16/2000 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*
04/07/2000 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*