Inspection History Details
Inspection Status: Denied
Inspection History: FRAMING
Permit Number - T99CM01105
Inspection Description - FRAMING
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2000 | FRAMING | Denied | IVRS - Inspection 0925* | |
| 06/02/2000 | FRAMING | Denied | IVRS - Inspection 0999*/1. PROVIDE BOND TO HOT AND COLD COPPER WATER LINES. 2. NO TEST ON HOT WATER LINES--MIN. TEST 50 PSI AIR. (BOTH LINES) 3. BEAM POST CONNECTION IN KITCHEN NOT INSTALLED PER UBC REQUIREMENTS. AND AT ENTRY. BOTH SIDES. 4. ALL METAL ELECTRIC BOXES NOT GROUNDED. 5. NO GAS PROVIDED TO DRYER/OR/NO 220 PROVIDE. 6. NO VENTALATION PROVIDED TO LAUNDRY AREA, PROVIDE EXHAUST FAN. 7. SUPPORT 90 DEGREE UTR AT KITCHEN. 8. NO BOND TO COPPER WATER LINES. 9. PROVIDE 2 GFCI AT MASTER VANITY OR CENTER SINGLE GFCI. 10. BOND ALL METAL BOXES. 11. CEILING AT ENTRY AND MID HOUSE NOT AT MIN. HEIGHT 7'-6" CURRENTLY AT 7' 0". 12. NO 120 VOLT POWER PROVIDE TO GAS STOVE. 13. BLOCK MECHANICAL 3 SIDES 14. SECURE ALL EXHAUST DUCTS AT ROOF. 15. MISSING ANCHOR BOLTS AT ALL SHEAR WALLS. NO APPROVED PLANS ON SITE. MET WITH BUILDER DURING INSPECTION. | |
| 05/31/2000 | FRAMING | Correction Required | ADDTL COMMS - NO ACCESS PROVIDED; GATES MUST BE OPEN | |
| 05/31/2000 | FRAMING | Denied | DENIED | |
| 03/15/2000 | FRAMING | Correction Required | ADDTL COMMS - NO ACCESS PROVE | |
| 03/15/2000 | FRAMING | Denied | DENIED | |
| 12/08/1999 | FRAMING | Denied | DENIED |