Inspection History Details
Inspection Status: Correction Required
Inspection History: FRAMING
Permit Number - T99CM01074
Inspection Description - FRAMING
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/02/1999 | FRAMING | Correction Required | ADDTL COMMS - 1. PLANS CALL FOR 1/2 A.B. AT 32 O.C. YOU HAVE 3/8 A.B. 2. COMPLETE MECHANICAL ROUGH IN. | |
| 07/02/1999 | FRAMING | Denied | IVRS - Inspection 0999* | |
| 06/25/1999 | FRAMING | Correction Required | ADDTL COMMS - INSTALL 1/2 DIAMETER ANCHOR BOLTS (THOSE INSTALLED ARE NOT 1/2 DIN) | |
| 06/25/1999 | FRAMING | Partial Approval | IVRS - Inspection 0000* | |
| 06/10/1999 | FRAMING | Partial Approval | IVRS - Inspection 0000* | |
| 06/07/1999 | FRAMING | Correction Required | ADDTL COMMS - GATE LOCKED | |
| 06/07/1999 | FRAMING | Not ready for Inspection | NOT READY FOR INSPECTION | |
| 05/10/1999 | FRAMING | Correction Required | ADDTL COMMS - 1. A35S LEDGER TO EACH STUD. 2. 1/2 DIAMETER ANCHOR BOLTS 36 ON CENTER SPACING PLATE BOLTS. 3. ANCHOR ALL FRAME WALLS TO EXISTING MASONRY AND FRAME WALLS. 4. STRAP TRIMMER STUDS TO HEADERS. 5. WALL BRACING EACH CORNER BOTH WAYS. | |
| 05/10/1999 | FRAMING | Denied | IVRS - Inspection 0999* | |
| 04/30/1999 | FRAMING | Correction Required | ADDTL COMMS - CORRECT # 1,2 &5 FROM INSPECTION ON 5/10 | |
| 04/30/1999 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000* |