Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T99CM01069
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/25/2000 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000* 1. ALL CORRECTIONS HAVE BEEN MADE 2. PLUMBING CONTRACTOR TO INSURE THAT TUB OVER FLOW DOES NOT LEAK |
|
09/22/2000 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* WATER TEST OK SECT 94 UPC 905.1 THIS IS THE 3RD DENIAL FOR VENT GRADE YOU MUST PAY A REINSPECTION FEE THIS IS THE 3RD DENIAL FOR VENT GRADE YOU MUST PAY A REINSPECTION FEE |
|
09/18/2000 | PLUMBING - INTERMEDIATE | Partial Approval | TEST ON COPPER ONLY NEED TEST ON ABS THANKS | |
09/08/2000 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* PLAN REVSION OK ON DWV AGAIN WATER CLOSET MUST HAVE 15" CLEAR TO SIDEWALL 408.5 AGAIN I MUST SEE WATER TEST TO 42" ON DWV 94 UPC 712.2 SEE 905.0 VENT PIPE GRADES AND CONNECTIONS |
|
09/07/2000 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* | |
09/06/2000 | PLUMBING - INTERMEDIATE | Denied | DWV SYSTEM NOT INSTALLED PER ISO METRIC DRAWING ON PLAN EITHER RE-PIPE PER PLAN OR REVISE DRAWING TO REFLECT INSTALLATION WATER CLOSET MUST HAVE MINMUM 15" CENTER TO SIDEWALL CLEAR NEED TO SEE PRESSURE TEST ON WATER PIPING NEED TO SEE WATER TEST ON DWV PIPING TO 42" NO COLD WATER TO EAST UNIT KITCHEN SINK SUPPORT COLD WATER PIPING AT SERVICE NEED SEPARATE INPECTION FOR GAS TO INCLUDE A. PLUMBERS TAPE NOT AN APROVED STRAP B. CAP OFF GAS TO ELECTRIC AC UNIT C. REVISE DRAWING TO REFLECT CHANGES THIS IS A LIST OF SOME OF THE VIOLATIONS ON THIS JOB BUT MAY NOT INCLUDE AL OF THE CODE VIOLATIONS PLEASE CHECK ALL WORK |
|
08/29/2000 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* | |
08/28/2000 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* INTERMEDIATE PIPING COVERED BEFORE INSPECTION ALL WORK MUST BE EXOSED FOR INSPECTION NO CHANGE SINCE LAST INSPECTION MUST PAY REINSPECTION FEE, AND HAVE ALL WORK EXPOSED |
|
07/08/2000 | PLUMBING - INTERMEDIATE | Denied | 1. PLANS CALL FOR 4" WATER CLOSETS AND VENT THRU ROOF |