Inspection Status: Correction Required
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T99CM01067
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/31/2000 | MECHANICAL - ABOVE CEILING | Correction Required | ADDTL COMMS - 1. SUPPLY/RETURN FLEX DUCT IN CRAWL SPACES OR ATTICS MUST BE R-6 2. FLEX DUCT IN CRAWL SPACE MUST BE ELEVATED 4 ABOVE SOIL 3. COMPLETE SUCTION LINE IWSOL. UP TO FAN COILS COMPLETELY IN ATTIC TO PREVENT DRIPING 4. BE SURE TO RUN PRIMARY AND SECONDARY COND. DRAINS TO SEPERATE LOCATIONS. | |
05/31/2000 | MECHANICAL - ABOVE CEILING | Partial Approval | PARTIAL APPROVAL |