Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/29/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
|
| 02/11/2000 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - DENIED - NO ACCESS. RE-CALL. ARRANGE TO BE ON SITE. |
| 02/11/2000 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0920* |
| 06/16/1999 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. ALL ELECTRIC OK EXCEPT KITCHEN RELOCATION WIRES. OK TO INSULATE AND DRY WALL EXTERIOR WALLS AND CEILING AREAS EXCEPT WHERE PLUMBING AND MECHANICAL WILL BE. DO NOT COVER ANY PLUMBING OR MECHANICAL. |
| 06/16/1999 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 06/15/1999 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. GROUND ALL METAL ELECTRIC BOXES. 2. NAIL PROTECT ALL WIRES WITH IN 1 1/4 OF STUD SURFACE. 3. MAKE UP ALL GROUNDS IN ELECTRIC BOXES. 4. FILL ALL KOS IN SERVICE PANEL OUTSIDE. 5. FILL ALL NAIL HOLES IN 6X6 POST CAP. |
| 06/15/1999 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* |