Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
Permit Number - T99CM00941
Inspection Description - ELECTRIC - FINAL
Inspection Status - Not ready for Inspection
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/10/2000 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
| 04/06/2000 | ELECTRIC - FINAL | Correction Required | ADDTL COMMS - 1. SODA ROOF EQUIP. NEEDS DISC MEANS AND MOTOR LOAD PROTECTION ART 430. 2. INSTALL MISSING LIGHTS 3. INSTALL MISSING SHIELDS 4. SODA ROOF EQUIP TO 8C WIRED USING AN APPROVED WIRING METHOD. | |
| 04/06/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* | |
| 03/31/2000 | ELECTRIC - FINAL | Correction Required | ADDTL COMMS - 1. LIGHTING MISSING IN HARD CEILING 2. INSTALL BONDING BUSHINGS AT GUTTER AND PANELS 501-16 N.E.C. 3. OUTDOOR LIGHTING MUST COMPLY WITH CITY OF TUCSON LIGHT POLLUTION ORDINANCE 4. OPEN ALL EYS FITTINGS TO VERIFTY CHICO INSTALLATION 5. USE CODE APPROVED TRANSITION FROM CONDENSANG UNIT DISCONNECTS TO EQUIP. TERMINATIONS 6. NEED MIN 36 X 30 WIDTH OF WORKING CLEARANCE AT A.C. DISCONNECT. 7. USE PLASTIC BUSHINGS ON 1/2 NIPPLES AT A.C. UNITS 8. USE FACTORY CHASE NIPPLES NOT CUT CONNECTORS USED AS CHASE NIPPLES 9. SECURE SEALTIGHT TO PROTECT FROM FUTURE DAMAGE (SOUTH CONDENSING UNIT) | |
| 03/31/2000 | ELECTRIC - FINAL | Partial Approval | PARTIAL APPROVAL |