Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T99CM00941

Parcel: 14044018B


Addresses:

6261 E BENSON HY


Inspection Status: Partial Approval

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T99CM00941

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Partial Approval

Date Description Inspector Results Comments
01/31/2000 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*
01/28/2000 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*
01/26/2000 ELECTRIC - UNDERGROUND Correction Required ADDTL COMMS - NOT READY ALSO GROUND (LIGHTING ) PROTECTION SHOULD
01/26/2000 ELECTRIC - UNDERGROUND Denied IVRS - Inspection 0999*
01/24/2000 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*
01/20/2000 ELECTRIC - UNDERGROUND Correction Required ADDTL COMMS - PARTIAL POLE LIGHTS.
01/20/2000 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*
01/11/2000 ELECTRIC - UNDERGROUND Correction Required ADDTL COMMS - OK TO CLEAR TEMP SERVICE.
01/11/2000 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*
01/07/2000 ELECTRIC - UNDERGROUND Correction Required ADDTL COMMS - 1. BOND NEUTRAL TO ENCLOSURE AT SERVICE PER N.E.C. ART 250 2. BOND EQUIP GROUNDING BUS BAR TO NEUTRAL AT SERVICE 3. DONT USE SHEET ROCK SCREW (BOLT OR MCHINE THREADS) 4. DONT DOUBLE LUG ELEC TERMINATIONS UNLESS LUG IS APPROVED FOR 5. USE ANTI OX PASTE ON ALL ALUM TERM
01/07/2000 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*
12/28/1999 ELECTRIC - UNDERGROUND Partial Approval UNDERGRD PVC RUNS FROM
12/28/1999 ELECTRIC - UNDERGROUND Partial Approval GUTTERS INSIDE TO SOUTH
12/28/1999 ELECTRIC - UNDERGROUND Partial Approval END OF MAIN BLDG