Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/06/2004 |
BUILDING - FINAL |
|
Approved |
1) PER CONVERSATION WITH S. LONG ON 2/6/04 STUCCO MESH AND BLDG FINAL APPROVED PER B. STEVENS |
| 02/04/2004 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) STUCCO MESH HAS NOT BEEN APPROVED |
| 01/29/2004 |
BUILDING - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PARTIAL PENDING LOCK AND HOLD #2 |
| 12/12/2003 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) ADD GFCI OUTLET RT OF RANGE 2) PROTECT ELECTRICAL IN PORCH COLUMNS 3) LABEL MAIN PANEL BREAKERS 4) INSTALL ANTI-SIPHON AT HOSE BIB 5) REPLACE COVERS ON GROUND LEVEL OUTLETS WITH WET AREA COVERS 6) ELECTRIC BOX LEFT OF PANEL MUST BE WEAHTER PROOF |
| 12/11/2003 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) NUMEROUS PROBLEMS THRU-OUT, HOUSE OCCUPIED. MUST MEET WITH HOME OWNER |
| 10/22/2003 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) FURNACE ENCLOSURE REQUIRES COMBUSTION AIR 2) WATER HEATER VENT MUST EXTEND VERTICALLY AT LEAST 5' 3) VANITIES AND KITCHEN SINK NOT INSTALLED |
| 07/08/2003 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |