Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date |
Description |
Inspector |
Results |
Comments |
| 07/19/2000 |
ELECTRIC - UFER |
|
Approved |
|
| 05/19/2000 |
ELECTRIC - UFER |
|
Correction Required |
ADDTL COMMS - GROUND ROD TO BE STRAIGHT NOT BENT WATER AND GAS BOND |
| 05/19/2000 |
ELECTRIC - UFER |
|
Partial Approval |
IVRS - Inspection 0000* |
| 04/17/2000 |
ELECTRIC - UFER |
|
Correction Required |
ADDTL COMMS - 1. REMOVE NEUTRAL TO GROUND BUS BAR 2. HOOD NOT ALLOWED ON SMALL APPLIANCE CIRCUIT GFI OUTSIDE NOT ALLOWED ON SMALL APPLIANCE CIRCUIT 3. STRAP CONDUIT AT SERVICE 4. NEED WEATHER PROOF FITTINGS OUTDOORS 5. NEED GROUNDING FOR SERVICE AND WATER AND GAS BOND 6. ANCHOR GUY BACK 7. NEED ROOF JACKS 8. NEED LICENSED ELECTRICAL CONTRACTOR |
| 04/17/2000 |
ELECTRIC - UFER |
|
Not ready for Inspection |
IVRS - Inspection 0000* |