Permit: T99CM00877

Parcel: 118040010

Inspection Status: Correction Required

Inspection History: FRAMING

Date Description Inspector Results Comments
10/26/1999 FRAMING Correction Required ADDTL COMMS - PROVIDE THAZ9 AT TRIPLE GIRDER IN GARAGE. PROVIDE FRAMING UNDER ENTRY TO 16 O.C. WALL AND CLIP TOP AND BOTTOM R5P4S. NEED A LETTER FROM TRUSS MFG THAT TRUSSES HAVE BEEN INSTALLED OK AND AS BUILD IS APPROVED BY AN ENGINEER. FIREBLOCK STG ROOM AT HOT WATER AT CEILING LINE. COMPLETE ELEC AT MASTER BATH
10/26/1999 FRAMING Denied IVRS - Inspection 0999*
10/20/1999 FRAMING Correction Required ADDTL COMMS - ADD STUD TO SUPPORT 4 BANG BOX IN MASTER BEDROOM. SEPERATE ELECTRICAL WIRE ON INTERIOR WALL - CANNOT BE TIED TOGETHER IN A 24 SPAN. NEED FIRE STOP ON EAST AND WEST WALLS. NEED APPROVED TRUSS CALCULATION ON JOB SITE. NEED HIP SUPPORTS AS PER PLAN. PROVIDE 3 SIDE SUPPORT ON REGISTERS. PROVIDE FIRESTOP IN HALL BATHROOM TO PROTECT RAFTERS
10/20/1999 FRAMING Denied IVRS - Inspection 0999*