Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Correction Required
Inspection History: MECHANICAL - FINAL
Permit Number - T99CM00715
Inspection Description - MECHANICAL - FINAL
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/01/2000 | MECHANICAL - FINAL | Correction Required | ADDTL COMMS - MECH SYSTEMS CHECKING STATUS OF SMOKE ALARMS | |
02/01/2000 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* | |
09/21/1999 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* |