Permit: T99CM00670

Parcel: 114467340

Inspection Status: Correction Required

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T99CM00670

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Correction Required

Date Description Inspector Results Comments
03/18/1999 EXT METAL CLIPS/EXT SHEATHING Correction Required ADDTL COMMS - OKAY TO COVER 1. NEED MORE NAILS IN HEADER FRONT BEDROOM WEST WALL. 2. SD4/7 SHEAR TRANSFER NEED DETAIL FOR THIS SITUATION FOR INTERMEDIATE INSPECTION. 3. NEED HANGERS FOR IJIS ANGLE LEDGER FRONT BEDROOM. 4. SEE ROOF FRAMING PLAN CALLS FOR MULTIPLE STUDS UNDER BEAM FRONT ENTRY YOU HAVE ONE BEARING STUD. 5. REAR PORCH DETAIL CALLS FOR 4X4 POST B EDC 44 HARDWARE.