Inspection History Details
Inspection Status: Correction Required
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T99CM00611
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/31/2000 | ELECTRIC - INTERMEDIATE | Correction Required | ADDTL COMMS - EAST SECTION 1. SUB PANEL IN BATHROOM REQUIRED TO 30 WIDE IN FRONT 36 OUT AWAY FOR CLEARANCE. 2. PLANS HAVE NO OUTSIDE LIGHTING ON THEM. WEST 1. PLASTER RINGS-BATH RM LIGHTS 2. SW IN BATH S SIDE-STRAP W/IN 3 BOTH SIDES. | |
03/31/2000 | ELECTRIC - INTERMEDIATE | Denied | DENIED | |
12/29/1999 | ELECTRIC - INTERMEDIATE | Correction Required | ADDTL COMMS - 1. PERMANENTLY LABEL SERVICES FOR ADDRESSING 2. USE GROUNDING BUSHING WHERE CONCENTRICS ENCOUNTERED AT SERVICE EQUIPMENT 3. INSTALL REJECT PINS OK TO CLEAR TEMP SER 4014 N ORACLE CALLED IN 3PM | |
12/29/1999 | ELECTRIC - INTERMEDIATE | Partial Approval | OK CHANGE OVER ON SERVIC |