Inspection Status: Correction Required
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/31/2000 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - EAST SECTION 1. SUB PANEL IN BATHROOM REQUIRED TO 30 WIDE IN FRONT 36 OUT AWAY FOR CLEARANCE. 2. PLANS HAVE NO OUTSIDE LIGHTING ON THEM. WEST 1. PLASTER RINGS-BATH RM LIGHTS 2. SW IN BATH S SIDE-STRAP W/IN 3 BOTH SIDES. |
| 03/31/2000 |
ELECTRIC - INTERMEDIATE |
|
Denied |
DENIED |
| 12/29/1999 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. PERMANENTLY LABEL SERVICES FOR ADDRESSING 2. USE GROUNDING BUSHING WHERE CONCENTRICS ENCOUNTERED AT SERVICE EQUIPMENT 3. INSTALL REJECT PINS OK TO CLEAR TEMP SER 4014 N ORACLE CALLED IN 3PM |
| 12/29/1999 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
OK CHANGE OVER ON SERVIC |