Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/01/2005 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* |
| 03/15/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* FINAL SUBJECT TO BLDG INSP. DETERMINATION OF EXIT LIGHTING |
| 03/14/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* 1) SECURLY MOUNT A/C DISCONNECTS TO STAND 2) BLDG INSP. TO DETERMINE IF EXIT LIGHTING REQUIRED |
| 03/05/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* 1) NEED PERMANENT METAL ADDRESS LABELS 2) LABEL PANEL 3) MOVE RECEPTICLE FROM BEHIND SINK 4) LABEL SUB PANEL AND ALL BREAKERS 5) PROTECT RECEPTICLE FROM WOOD AND MISSING FACE PLATE 6) MISSING FACE PLATES 7) WORKING CLEARANCES IN FRONT OF A/C DISCONNECTS 8) BUILDING INSP. TO DETERMINE IF EXIT LIGHTING IS REQUIRED. CHECK ROOF CONNECTIONS |