Permit: T99CM00394

Parcel: 11931022Q

Inspection Status: Correction Required

Inspection History: FRAMING

Permit Number - T99CM00394

Inspection Description - FRAMING

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/05/2000 FRAMING Correction Required ADDTL COMMS - 1. PROVIDE PROOF OF SHOWER VALVE ANTI SCALD REQUIREMENT PER UPC. 410.7.
01/05/2000 FRAMING Partial Approval IVRS - Inspection 0000*
01/04/2000 FRAMING Correction Required ADDTL COMMS - ENGINEER REVISE PLANS OK, ALL OTHER INSPECTIONS OK, MISSING ANCHOR BOLTS TWO MINIMUM SINGLE SOLE PLATE AND 12 MINIMUM FROM ENDS.
01/04/2000 FRAMING Denied IVRS - Inspection 0999*
12/29/1999 FRAMING Correction Required ADDTL COMMS - WAITING FOR PLAN REVISIONS & ENGINEERING. ALL AREAS THAT NEED REVISIONS WILL NEED TO BE INSPECTED. CONTRACTOR CONTINUE AT YOUR OWN RISK. THIS INCLUDES ANY SHEAR WALL CHANGES. INTERMEDIATES MUST BE APPROVED BEFORE SHEETROCK IS APPLIED
12/29/1999 FRAMING Partial Approval IVRS - Inspection 0000*
12/20/1999 FRAMING Correction Required ADDTL COMMS - PLANS NEED TO BE REVISED TO AS BUILT. ALL INTERIOR BEARING WALLS REPLACED WITH BEAM MUST BE SHOWN. EPIS AT SOUTH/EAST PORTION OF HOUSE AT TOP PLATE, PROVIDE DETAIL FOR AS BUILT. (AT EXTERIOR WALLS) REVISE PLUMBING PLAN AND FLOOR PLAN FOR MASTER. REVISE GARAGE, HOT WATER ROOM, ENTRY.
12/20/1999 FRAMING Denied IVRS - Inspection 0999*
12/19/1999 FRAMING Correction Required ADDTL COMMS - 2. SECURE ALL DWERTER VALVES 3. CHECK COUNTER FOR OUTLET REQ 4. ADD GFCI AT DBL. LAV 5. NEED O.S.B SHEAR AT # 6 WALL INTERIOR, BLOCK AT TOP AND ANCHOR BOLTS 6. HEARTH SAFETY CLIP 7. BLOCK MECH VENTS SIDES
12/19/1999 FRAMING Not ready for Inspection IVRS - Inspection 0000*