Permit: T99CM00369

Parcel: 123052460


Addresses:

2230 N NORTON AV

Inspection Status: Correction Required

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
02/19/1999 BUILDING - FINAL Correction Required ADDTL COMMS - HOUSE LOCKED AT 9:20. APPROVED LATER IN THE DAY BY WES WRIGHT AT HENRY DURAZO REQUEST.
02/19/1999 BUILDING - FINAL Denied IVRS - Inspection 0920*
02/10/1999 BUILDING - FINAL Correction Required ADDTL COMMS - 1. PANEL APPEARS TO BE OVER LOADED C/BS DOUBLE LUGGED. 2. GFCI PROTECTION ON OUTSIDE RECEPTS. 3. 2 WASTE FOR WASHER REQUIRED. 4. CAP OFF OR INSTALL SINK AT LAUNDRY TUB. 5. 4 WIRES REQUIRED FOR DRYER ELEC SUPPLY. 6. EXHAUST FAN REQUIRED IN LAUNDRY ROOM. 7. DESIGNATED RECEPT FOR WASHER. 8. WORK WAS PREVIOUSLY COMPLETE ANC COVERED. 9. SMOKE DETECTORS NEEDED IN BEDROOMS.
02/10/1999 BUILDING - FINAL Denied IVRS - Inspection 0999*