Permit: T99CM00362

Parcel: 106060180


Addresses:

1320 W PRINCE RD


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T99CM00362

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/01/2009 BUILDING - FINAL Approved
08/23/2007 BUILDING - FINAL Not ready for Inspection 1) REPAIR RESTROOM EXHAUST FAN DUCTS.

2)HALOGEN LIGHTS HAZARDOUS. REMOVE ALL ILLEGALLY INSTALLED WIRING.

3) AIR HANDLER/ MECHANICAL SPACE ABOVE THE RESTROOM IS FOR THE SAV-A-LOT NEXT DOOR. PROVIDE ACCESS TO THIS SPACE FROM THE SAV-A-LOT TENANT AREA.

4) RESTROOM SHOULD HAVE CORRECT ACCESSIBLE HARDWARE AND GRAB-BARS.

5) SPACE # 1328 HAS INSTALLED A ROLL UP DOOR IN THE BACK WITHOUT PROPER PERMITS OR INSPECTION. PERMITS MUST BE OBTAINED AND THAT SPACE WILL ALSO REQUIRE A CofO.

6) TENANT SPACE 1354 APPEARS TO HAVE ILLEGALLY ANNEXED SPACE 1352. PLANS AND A NEW CofO WILL NEED TO BE OBTAINED. CURRENT CofO ISSUED AFTER TI IN 1999 IS FOR 7700 SQUARE FEET.

7) THE CHECK CENTER AT THE WEST END OF THE MALL NEEDS TO HAVE THE SIGNAGE ON THE SOUTH WALL INSTALLED PER THE NEC.

8) ALL ELECTRIC WIRING IN THE EXTERIOR SOFFITS NEEDS TO BE BROUGHT UP TO CODE BY A LICENSED ELECTRICAL CONTRACTOR.

9) THE ROOF TOP EXAUST VENTS AT THE LAUNDRY ARE TO TERMINATE WITH A 180 DEGREE BEND SO THAT WATER WILL NOT ENTER BUILDING.