Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/29/2000 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 12/27/2000 |
BUILDING - FINAL |
|
Denied |
1. ADDRESS 3232 MUST BE ON HOUSE MIN. 3' NUMBERS. 2. CLIP PORCH RAFTERS. 3. DEAD FRONT REQUIRED ON SERVICE PANEL. LABLE ALL CIRCUITS. 4. ANTI SIPHON VALVE REQUIRED ON OUTSIDE HOSE BIB. 5. SHUT OFF VALVE REQUIRED UP STREAM OF UNION WITHIN 36" OR USE LEFT AND RT. HANDED COUPLING. 6. ISOLATED NEUTRAL BAR REQUIRED ON SUB PANEL. 7. 14 GA WIRE CANNOT BE ON 20 AMP BREAKER 15A MAX. 8. BARE BULB FIXTURE NOT ALLOWED IN CLOSET. 9. FIRE PROOF CAULK FIREPLACE PENETRATION. |