Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T99CM00222
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/18/2001 | BUILDING - FINAL | Approved | IVRS - Inspection 0000* | |
05/16/2001 | BUILDING - FINAL | Partial Approval | ||
04/11/2001 | BUILDING - FINAL | Denied | IVRS - Inspection 0999*/1. GFCI AT HALL BATH LEFT END DOESN'T TRIP (UPSTAIRS) NOTE: THIS OUTLET NOT PLACED PER PLAN. 2. PATCH OR FIRETAPE IN PLUMBING BOX UNDER STAIRWAY. 3. CORRECT STANDING WATER UNDER HOUSE. 4. PROVIDE CRAWLSPACE LIGHTING PER CODE. 5. PROVIDE COT APPROVAL FOR ADDED FORCED AIR UNIT UPSTAIRS. 6. MISSING RECEPTICLE NEAR PATIO DOOR IN LIVINGROOM. 7. LIGHT FIXTURE IN CLOSET OF BEDROOM #1 DOES NOT COMPLY WITH NEC 410-8. 8. IDENTIFY TRUE CLEANOUTS AND ELIMINATE OTHERS. 9. PROVIDE GAS PRESSURE TEST. | |
02/05/2001 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/LOCKED. ADDRESS TO BE VISIBLE FROM STREET CORRECT ALL ITEMS LISTED BEFORE RECALLING. | |
03/27/2000 | BUILDING - FINAL | Correction Required | ADDTL COMMS - DENIED - 1. NO GAS PRESSURE TEST. 2. PROVIDE APPROVED PRIOR INSPECTIONS AS PREVIOUSLY ADVISED. 3. PERMANENT ADDRESS REQUIRED. 4. IDENTIFY GFCI CIRCUIT EXTERIOR AT PANEL. 5. DO NOT CALL FOR ANOTHER INSPECTION UNTIL ALL ITEMS ARE COMPLETE AND SECURED OR YOU WILL BE REQUIRED TO PAY A RE-INSPECTION FEE. 6. PROVIDE ACCESS TO GARAGE. 7. CAULK ELECTRICAL PENETRATION AT GARAGE. | |
03/27/2000 | BUILDING - FINAL | Denied | DENIED | |
02/15/2000 | BUILDING - FINAL | Correction Required | ADDTL COMMS - 1. INSTALL PERMANENT ADDRESS NUMBERS. 2. NEED TO VARIFY ALL INTERMEDIATE APPROVALS. 3. COMPLETE GRADING. CUT SEWER C.O. TO GRADE. 4. EXTEND H20 HEATER. PTR LINE EXTERIOR 3-18 OF GROUND. 5. PAINT EXPOSED VTRS. 6. NEED ROOF ACCESS TO INSPECT AC UNITS. | |
02/15/2000 | BUILDING - FINAL | Denied | IVRS - Inspection 0999* | |
02/09/2000 | BUILDING - FINAL | Correction Required | ADDTL COMMS - 1. BOTH GFCI CIRCUITS ARE NOT FUNCTIONING CORRECTLY. 2. NO GAS BOND. 3. WIRING IN THE GARAGE MUST BE PROTECTED. 4. MANY PREVIOUS INSPECTIONS ARE NOT SIGNED OFF. | |
02/09/2000 | BUILDING - FINAL | Denied | IVRS - Inspection 0999* |