Inspection Status: Correction Required
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/30/2000 |
MECHANICAL - FINAL |
|
Correction Required |
ADDTL COMMS - NOTE! MECHANICAL FINAL CONTINGENT ON ELECTRICAL FINAL APPROVAL |
| 03/23/2000 |
MECHANICAL - FINAL |
|
Correction Required |
ADDTL COMMS - 1. PAINTED PVC IS OK 2. ADDITIONAL HANGERS ARE OK 3. EXISTING BOILER CANNOT BE IN THE SAME ROOM AS THE CONDENSORS. |
| 03/23/2000 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 03/22/2000 |
MECHANICAL - FINAL |
|
Correction Required |
ADDTL COMMS - 1. CHILLER INSTALLED IN WITH A HOT WATER HEATING BOILER WITH NO SEPERATION. |
| 03/22/2000 |
MECHANICAL - FINAL |
|
Denied |
DENIED |
| 02/17/2000 |
MECHANICAL - FINAL |
|
Correction Required |
ADDTL COMMS - 1. NEED ADDITIONAL HANGARS, CHANGE OF DIRECTION, TOWER COND WATER, DOWN INTO CONDENSERS 2. PVC LOCATED AT TOWER NEEDS TO BE PAINTED W/SYNTHETIC LATEX PAINT 3. BE SURE TO CALL PRIOR TO FINAL INSPECTION TIME |
| 02/17/2000 |
MECHANICAL - FINAL |
|
Partial Approval |
PARTIAL APPROVAL |