Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/19/2001 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 04/17/2001 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1. MUST EXPOSE C.O. FOR KIT. SINK.2. WATER HTRS CAN ONLY HAVE 1-12" FLEX LINE ON P & T. 3.MUST PROVIDE VACUME BREAKERS AT HOSE BIB IN MECH RM. 4. MUST SECURE DISHWASHER HOSE DRAIN AS HIGH AS POSSIBLE UNDER COUNTER. |
| 05/02/2000 |
PLUMBING - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 04/28/2000 |
PLUMBING - FINAL |
|
Denied |
DENIED |
| 04/05/2000 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999* |