Inspection Status: Closed
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/23/2010 |
PLUMBING - FINAL |
|
Closed |
|
| 07/30/1999 |
PLUMBING - FINAL |
|
Partial Approval |
PARTIAL APPROVAL |
| 07/29/1999 |
PLUMBING - FINAL |
|
Correction Required |
ADDTL COMMS - 1. WATER HTR DOES NOT HAVE DRIP PAN OR DRAIN OR PAN AS PER PLAN, 2. NO CO @ BAR SINK NEXT TO HAND SINK PLAN DOES NOT SHOW THIS FIXTURE. 3. 3-COMP, SINK FLOW CONTROL NOT VENTED AS PER PLAN. 4. NEED LISTING FOR H.C. LAVATORYS FOR ADA APPROVAL OR WILL REUQIRED TO HAVE OFFSET TAIL PC. 5. 3- COMP. SINK MUST HAVE DRAINAGE FITTING @ CONTINUOUS WASTE. 6. P-TRAPS FOR HAND SINKS NOT WHAT IS SPELOUT ON PLAN. (17 GA P.TRAP W/CO. |
| 07/29/1999 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0000* |
| 07/28/1999 |
PLUMBING - FINAL |
|
Correction Required |
ADDTL COMMS - FLOW CONTROLL NOT INSTALLED DRAIN FOR BACKFLOW DEVICE PLEASE INSTALL RELIEF LINE 1 ABOVE FLOOD RIM OF MOP SINK FLOOR CO MISSING. |
| 07/28/1999 |
PLUMBING - FINAL |
|
Not ready for Inspection |
NOT READY FOR INSPECTION |