Inspection Status: Correction Required
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 01/11/2000 |
ELECTRIC - CABLE DROP |
|
Correction Required |
ADDTL COMMS - OK TO CLEAR NOTE ACORN CLAMPS ARE TERMINATED INCORRECTLY W/GROUNDING ELECTRODE CONDUCTOR |
| 01/06/2000 |
ELECTRIC - CABLE DROP |
|
Correction Required |
ADDTL COMMS - 1. USE SCH 80 PVC WHERE EXPOSED 2. INSTALL (TERMINATE) GROUNDING ELECTRODE CONDUCTOR DIRECTLY TO NEUTRAL BUS BAR AT PEDASTEL |
| 01/06/2000 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0999* |