Permit: T99BU03439

Parcel: 136417960


Addresses:

10272 E LUCILLE DR


Inspection Status: Correction Required

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Permit Number - T99BU03439

Inspection Description - EXCAVATION/LAYOUT REBAR & ZON

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/05/2000 EXCAVATION/LAYOUT REBAR & ZON Correction Required ADDTL COMMS - 1. PROVIDE #5 VERTICALS AT 48 CC AND 2-#5 VERTICALS AT 24CC. 2. PROVIDE TRANSVERSE #5 BARS IN ADDITION TO THE TAILS OF THE VERTICALS.
01/05/2000 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection 0000*
12/30/1999 EXCAVATION/LAYOUT REBAR & ZON Correction Required ADDTL COMMS - 1. LOCATE FACE OF WALL, ON THE LOW SIDE, 6 FROM EDGE OF FOOTING. 2. PROVIDE TRANSVERSE #4 X 26 @ 24O.C. IN ADDITION TO THE TAILS OF THE VERTS. 3. VERTS. ARE TO BE #5S. 4. CONFIRM PROJECT IS ON THE CORRECT SIDE OF PROPERTY LINE.
12/30/1999 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection NOT READY FOR INSPECTION
12/29/1999 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection 0000*
12/23/1999 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection 0000*