Inspection Status: Correction Required
Inspection History: STEM WALL/RETAINING WALL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/12/2000 |
STEM WALL/RETAINING WALL |
|
Correction Required |
ADDTL COMMS - 1. PROVIDE VERTICALS AT NORTH END. 2. LAP BOND BEAMS 40 DIAMETERS (20 FOR #4). 3. EXTEND BOND BEAM STEEL TO THE END OF THE WALL. 4. COMPLETE BOND BEAM AT NORTH END. |
| 01/12/2000 |
STEM WALL/RETAINING WALL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 01/10/2000 |
STEM WALL/RETAINING WALL |
|
Correction Required |
ADDTL COMMS - LAY STEM BEFAORE INSPECTION. |
| 01/10/2000 |
STEM WALL/RETAINING WALL |
|
Denied |
DENIED |
| 01/05/2000 |
STEM WALL/RETAINING WALL |
|
Correction Required |
ADDTL COMMS - INDICATE WHAT PLAN YOU ARE USING, THE 1.83OR THE 3.83 RETAINING WALL. BOTH PLANS CALL FOR #5 VERTICALS. PLANS CALL FOR A #5 VERTICAL AT P. LASTERS (THIS MEANS YOU SHOULD DRILL INTO EXISTING FOOTING). STEM WALL NOT BUILT. CALL WHEN CORRECTED. |
| 01/05/2000 |
STEM WALL/RETAINING WALL |
|
Denied |
IVRS - Inspection 0999* |
| 12/30/1999 |
STEM WALL/RETAINING WALL |
|
Not ready for Inspection |
NOT READY FOR INSPECTION |