Inspection Status: Denied
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 07/06/2000 |
ELECTRIC - CABLE DROP |
|
Denied |
ATTACH GROUNDING ELECTRONE CONDUTOR DIRECTLY TO NEUTRAL BUS NOT EQUIP GROUNDING LUG |
| 12/20/1999 |
ELECTRIC - CABLE DROP |
|
Correction Required |
ADDTL COMMS - OK TO CLEAR TEMP POWER |
| 12/17/1999 |
ELECTRIC - CABLE DROP |
|
Correction Required |
ADDTL COMMS - 1. TEMP WIRING STILL NEEDS TO BE INSTALLED AT PROPER DEPTH 24 REQD FOR DIRECT BURIAL CONDUCTORS (2) INSTALL THE GROUNDING ELECTRODE CONDUCTOR DIRECTLY TO THE NEUTRAL BUS BAR AT THE PEDASTAL |
| 12/17/1999 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0999* |