Permit: T99BU00607

Parcel: 135050750


Addresses:

6350 E CALLE ORION

Inspection Status: Correction Required

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
03/11/1999 EXCAVATION/LAYOUT REBAR & ZON Correction Required ADDTL COMMS - APPROVED AS NOTED: 1. PROVIDE 12 LAPS AT FOOTING #3 CONTINUOUS STEEL. 2. PROVIDE EITHER: A) #4 VERTICAL REBAR AT 48 CC IN ADDITION TO VERTICAL REINF AT CORNERS, ENDS, AND JAMBS. B) #3 VERTICAL REBAR AT 24 CC IN ADDITION TO VERTICAL REINF AT CORNERS, ENDS. AND JAMBS. NOTE: REBAR IS REQUIRED TO HAVE A MINIMUM OF 40 DIAMETER LAPS.