Inspection Status: Correction Required
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/07/1998 |
MECHANICAL - FINAL |
|
Correction Required |
ADDTL COMMS - 1. HEAT PUMP - DOES UNIT HAVE AUX. LT. STRIP? IF YES, WHAT SIZE? MARK ELECTRICAL DATA PLATE TO CHECK IF UNIT PROPERLY FUSED. 2. CONCEAL CONTROL WIRING, DO NOT ALLOW SUN TO DAMAGE. 3. PICK UP FLEX SUPPLY/RETURN DUCTING IN CRAWL SPACE. CANT BE IN CONTACT WITH GROUND. |
| 12/07/1998 |
MECHANICAL - FINAL |
|
Denied |
SEE COMMENTS |