Permit: T98CM05789

Parcel: 128122200


Addresses:

4818 E 18TH ST

Inspection Status: Correction Required

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/25/1999 ELECTRIC - INTERMEDIATE Correction Required ADDTL COMMS - 1. STAPLE WIRES MAX 6 FROM BOXES.
04/12/1999 ELECTRIC - INTERMEDIATE Correction Required ADDTL COMMS - 1. 20 AMP GFCI CURCUIT FOR BATH GFI COMPLETE CIRCUIT ON ITS OWN. 2. NEED A SEPARATE CIRCUIT FOR COOLER. 3. NEED A SEPARATE CIRCUIT FOR HEATER (CHECK WATTAGE OF UNIT). 4. ALL LIGHTING CAN GO ON ONE CIRCUIT.\ 5. SCUTTLE HOLE TO MAINTAIN J-BOXES. 6. MOVE ATTIC VENT FROM OLD HOUSE TO EXTERIOR OF NEW ROOM.
04/12/1999 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*