Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T98CM05155
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Not ready for Inspection
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2000 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* | |
| 05/31/2000 | ELECTRIC - INTERMEDIATE | Correction Required | ADDTL COMMS - NOTES: GROUNDING ELECTRODE CONDUCTOR CANNOT BE SPLICED EXCEPT BY APPROVED METHOD CURRENT CARRING CONDUCTORS LARGER THAN #4 NEED TO BE BUSHED AT ALL POINTS OF ENTRANCE AND EXITS OF J-BOXES DISC. SWITHCES, PANELS. NEC 300-4F CONDUIT TO BE STRAPPED OR SUPPORTED WITH 3 OF J-BOX GROUND BAR IN STORE ROOM PANEL NEEDS TO BE BONDED TO THE GROUND SYSTEM INSTALL NEUTRALS AND GROUND CONDUCTORS IN CORRECT LOCATIONS BREAKER PANLE IN STORAGE ROOM MOUNTED TO HIGH A.F.F SHOULD BE 62 TO TOP BREAKER SPACE. | |
| 05/31/2000 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245* |