Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T98CM05155

Parcel: 13325186F

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T98CM05155

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
07/14/2000 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
05/31/2000 ELECTRIC - INTERMEDIATE Correction Required ADDTL COMMS - NOTES: GROUNDING ELECTRODE CONDUCTOR CANNOT BE SPLICED EXCEPT BY APPROVED METHOD CURRENT CARRING CONDUCTORS LARGER THAN #4 NEED TO BE BUSHED AT ALL POINTS OF ENTRANCE AND EXITS OF J-BOXES DISC. SWITHCES, PANELS. NEC 300-4F CONDUIT TO BE STRAPPED OR SUPPORTED WITH 3 OF J-BOX GROUND BAR IN STORE ROOM PANEL NEEDS TO BE BONDED TO THE GROUND SYSTEM INSTALL NEUTRALS AND GROUND CONDUCTORS IN CORRECT LOCATIONS BREAKER PANLE IN STORAGE ROOM MOUNTED TO HIGH A.F.F SHOULD BE 62 TO TOP BREAKER SPACE.
05/31/2000 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*