Inspection Status: Correction Required
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 02/02/1999 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - HAVE THESE FOR FINAL INSPECTION: 1. SUBMIT A LOAD CALCULATIION FOR THE ELECTRIC PANEL INCLUDE ELECTRIC WALL HEATER. 2. BATHROOMS REQUIRE A SEPARATE GFI CIRCUIT AT 20 AMPS. 3. ADD A RECEP ON WALL NEXT TO DOOR. 4. THE CIRCUIT BREAKERS IN THE PANEL MUST BE OF THE SAME MANUFACTURE AS THE PANEL. |
| 01/27/1999 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. SMOKE DETECTORS IN NEW CONSTRUCTION MUST BE HARD WIRED AND MUST HAVE 3 WIRES BETWEEN THEM FOR COMMON ALARM. BATTERY ONLY SMOKE DETECTORS ARE ALLOWED EXISTING COSTRUCTION ONLY. 2. USE A BOX APPROVED FOR FAN INSTALLATION IN BEDROOM. 3. MOVE WIRING AND DEVICE BOXES OUT OF MEDICINE CABINET AREA. 4. OPEN LAMP/BULB (KEYLESS TYPE -OR- PULL CHAIN) DEVICES ARE NOT ALLOWED IN CLOTHES CLOSETS. YOU MAY NEED TO ADD SWITCHES FOR THESE LIGHTS. 5. SUBMIT A LOAD CALCULATION FOR THE ELECTRIC PANEL INCLUDE ELECTRIC WALL HEATER. 6. BATHROOMS REQUIRE A SEPARATE GFI CIRCUIT AT 20 AMPS. 7. ADD AN EXTERIOR RECEPTACLE ON A GFI CIRCUIT. 8. ADD A RECEP ON WALL NEXT TO DOOR. 9. THE CIRCUIT BREAKERS IN THE PANEL MUST BE OF THE SAME MANUFACTIRE AS THE PANEL. |
| 01/27/1999 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* |