Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Not ready for Inspection
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 12/31/1998 |
EXT METAL CLIPS/EXT SHEATHING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 12/21/1998 |
EXT METAL CLIPS/EXT SHEATHING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 12/17/1998 |
EXT METAL CLIPS/EXT SHEATHING |
|
Correction Required |
ADDTL COMMS - 1. SHEAR WALL #6 BLKS WRONG HEIGHT. 2. GABLE END BRACIGN NOT IN L/D2 NEEDS TO BE NAILED FROM ABOVE. 3. HOLD DOWNS NOT TIGHT. 4. SHEAR WALLS REQUIRE STUD SPACING TO BE 16 ALONG WITH THE NAILING (CHECK THROUGHOUT). 5. SHEAR WALL #8 MISSING IN GARAGE. 6. W/D2 SHEAR TRANSFERS NOT IN. 7. SHEAR WALL #8 REQUIRES 8D 4 O.C. AT EDGES. |
| 12/17/1998 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999* |