Inspection History Details
Inspection Status: Correction Required
Inspection History: FRAMING
Permit Number - T98CM04394
Inspection Description - FRAMING
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/05/1999 | FRAMING | Correction Required | ADDTL COMMS - 1. PROVIDE CITY OF TUCSON AND ARCHITECT OF RECORD DETAIL OF SHEAR TRANSFER FOR INTERIOR DRYWALL AT INTERSECTING INTERIOR WALLS. 2. PLAN CALLS FOR SSTB16 ANCHOR BOLTS EPOXY BOLTS INSTALLED. PROVIDE CITY OF TUCSON AND SAME AS PRIOR INSPECTIONS. | |
01/05/1999 | FRAMING | Denied | IVRS - Inspection 0999* | |
12/30/1998 | FRAMING | Denied | IVRS - Inspection 0160* | |
12/24/1998 | FRAMING | Correction Required | ADDTL COMMS - 1. PLAN REVISION FOR SHEAR TRANSFER AT CHANELS NOT COMPLIED WITH. 2. INCORRECT EPOXY HAS BEEN USED AT HOLD DOWNS, EPOXY SET REQUIRED PROVIDE APPROVED REPAIR. 3. HEADERS NOT PROPERLY SHIMMED. DOUBLE TOP PLATES BOWED CHECK ALL. 4. KITCHEN PEX NOT CONNECTED. | |
12/24/1998 | FRAMING | Denied | IVRS - Inspection 0160* | |
12/18/1998 | FRAMING | Correction Required | ADDTL COMMS - 1. YOU MUST HAVE ALL PRIOR INSPECTION FORMS ON SITE FOR ALL INSPECTIONS. 2. PROVIDE PROOF OF INSPECTION FOR SITE LAYOUT, PRE SLAB AND UFER INSPECTIONS. 3. PROVIDE PRIOR FAILURE INSPECTION OF EXTERIOR CLIP. 4. INSPECTION ITEMS FROM 12/17/98 NOT COMPLIED WITH ITEM 1,2,3. 5. HEADERS NOT PROPERLY SHIMMED AT TOP PLATES. 6. INCORRECT STUD BOLTS AT HD5A HOLD DOWNS. 7. FIRE BLOCK CHASE AT BEDROOM. 8. SHEAR PANEL 7 NOT NAILED. | |
12/18/1998 | FRAMING | Denied | DENIED | |
12/17/1998 | FRAMING | Correction Required | ADDTL COMMS - INCORRECT HOLD DOWN BOLTS INSALLED. 2. FIRE BLOCK CHASE IN GARAGE. 3. SHEAR WALL 8 NAILED TO STUDS SPACED GREATER THAN 16 O.C. AND GREATER THAN 4 O.C. ON ENDS AND EDGES. 4. GAS NOT INSTALLED. 5. FIRE PLACE NOT PROPERLY INSTALLED. 6. STOPPED INSPECTION HOUSE NOT READY. TOO MANY ITEMS | |
12/17/1998 | FRAMING | Denied | DENIED |