Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T98CM04390

Parcel: 11306179A


Addresses:

3232 N WILSON AV

Inspection Status: Denied

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/05/2000 ELECTRIC - INTERMEDIATE Denied DENIED/1. 10 X 3 WINDOW HEADER REQUIRES DOUBLE TRIMMERS EACH END. 2. FLASHING REQUIRED AT WALL ROOF CONNECTION BETWEEN EXISTING AND ADDITION. 3. SKYLIGHT NOT PROPERLY INSTALLED/PROPERLY FLUSHED. 4. WASHER WASTE AND VENT NOT INSTALLED. 5. GAS LINE TO BE RE ROUTED. 6. PLUMBING NOT COMPLETE. 7. EXISTING WASHER NOT VENTED. 8. ENTRY WALLS REQUIRE ANCHOR BOLTS. 9. ELECTRIC SUB PANEL NOT WIRED. 10. CLOSET REQUIRE CEILING BLOCKING AND BATH. 11. FIRE BLOCK ALL DROPPED CEILINGS. 12. BATH EXHAUST FAN NOT PROPERLY INSTALLED--TURN 90 DEGREES. 13. DUCT WORK COMPLETE. BLOCK DEFUSERS 3 SIDES. 14. NAIL PROTECT ALL PLUMBING. 15. FIRE BLOCK ALL FURRED WALLS. 16. SUB PANEL MUST HAVE AN ISOLATED NEUTRAL. 17. ALL JUNCTION BOXES FOR ELECTRIC MUST BE ACCESSABLE. 18. ELECTRIC NOT PER PLAN. 19. ELECTRIC SERVICE REQUIRES 2" MUST PROPERLY ANCHORED. 20. RELOCATE ELECTRIC SERVICE TO PROVIDE ACCESSIBILITY AND 30 X 30 WORK AREA. 21. ELECTRIC SERVICE REQUIRES 2 EACH 8FT LONG GROUND RODS SEPARATED AT LEAST 6 FEET APART CONNECTED TO THE SERVICE PANEL BY A CONTINOUS #4 GROUND WIRE.
12/03/1999 ELECTRIC - INTERMEDIATE Correction Required ADDTL COMMS - MISSING GFI EXTERIOR SIDE BEDROOMS OK ON ELECTRIC
12/03/1999 ELECTRIC - INTERMEDIATE Partial Approval PARTIAL APPROVAL