Inspection History Details
Inspection Status: Correction Required
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T98CM04342
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/04/1999 | ELECTRIC - INTERMEDIATE | Correction Required | ADDTL COMMS - 1. NO PLAN ON JOB SITE, CHECKED SERV PANEL (GENERAL REPAIR PERMIT) THERE ARE 2 COUNTER TOP CIRCUITS AND A DW/DISPOSAL. 2. OKAY TO CONTINUE, WILL CHECK OUTLETS AT FINAL. 3. ALREADY SHEET ROCKED. | |
02/04/1999 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
12/04/1998 | ELECTRIC - INTERMEDIATE | Correction Required | ADDTL COMMS - NO DAMAGE REPORT OR DRAWING/REPAIR DETAIL, CIRCUITS IN KITCHEN ARE ON #14 WIRE POSSIBLY OUTLETS ADDED IN KITCHEN, #14-3 ADDED FOR DISPOSAL, ALL BREAKERS IN SUB ARE 20 AMP?, SERVIE IS DOUBLE LUGGED TWICE ONCE AHED OF THE MAIN FUSES, KITCHEN IS PARTIALLY SHEETROCKED, MISSING SOME FIREBLOCKS, SERVICE DISCONNECT IS IN A HAZARDOUS STATE - PART OF FUSE RECEPTACLE IS BROKEN | |
12/04/1998 | ELECTRIC - INTERMEDIATE | Denied | DENIED |