Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 03/16/2001 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000* |
| 03/15/2001 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0225* YOUR UFER GROUND WAS NEVER APPROVED. THEREFORE YOU MUST DRIVE A 2ND GROUND ROD AND TIE BOTH GROUNDRODS TOGETHER WITH A #6 SOILD BARE COPPER WIRE TERMINATED AT THE NEUTRAL GROUND BAR IN THE PANEL |
| 02/22/1999 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0000* |