Inspection Status: Correction Required
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/01/1999 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - SET YOUR GROUND RODS PER DIAGRAM. BEAM POCKET OK |
| 02/25/1999 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 02/22/1999 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. RECEPTICALS BOXES ON CMV WALL NEED TO BE REPLACED WITH THE CORRECT BOXES. 2. ELECTRICAL NOT PER PLAN, REVISE PLAN OR CORRECT AS PER PLAN. 3. DRYER WIRE NEEDS TO BE A 10/4 WIRE AND GROUND TO PANEL. 4. UFER IS A #6 NEEDS TO BE A #4. |
| 02/22/1999 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0000* |