Permit: T98CM04150

Parcel: 128010440


Addresses:

6295 E 22ND ST


Inspection Status: Correction Required

Inspection History: ELECTRIC - FINAL

Permit Number - T98CM04150

Inspection Description - ELECTRIC - FINAL

Inspection Status - Correction Required

Date Description Inspector Results Comments
04/26/2000 ELECTRIC - FINAL Correction Required ADDTL COMMS - RESCHEDULE INSP GEN CONTRACTOR TO BE HERE W/APPROVED PLANS 1. INSTALL DISCONNECTING MEANS AT WATER HEATER 2. INSTALL BOX EXTENSIONS AS REQD PER ART 370 NEC
04/26/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
01/10/2000 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
01/07/2000 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
12/20/1999 ELECTRIC - FINAL Correction Required ADDTL COMMS - 1. SEAL OPEN K.O AT SERVICE 2. LIGHTING DOESNT MEET LIGHT POLLUTION CODE NEED SHOE BOX TYPE FIXTURE WITH FLUSH LENSE 3. POUR ALL EYS FITTINGS PRIOR TO FINAL INSPECTION AND HAVE THIS CONTRACTOR ON SITE TO OPEN FITTINGS AND CLOSE AT INSPECTION 4. INSTALL BUSHINGS AS REQUIRED WHERE #4 OR LARGER PASSES THROUGH PANEL AND CONDUITS 5. FINISH WALKING COOLERS 6. GROUND GROUNDING BUSHING PER N.E.C. USING THE EQUIP GROUNDING CONDUCTOR IN THE CONDUIT UTILIZED
12/20/1999 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*