Inspection History Details
Inspection Status: Correction Required
Inspection History: ELECTRIC - FINAL
Permit Number - T98CM04150
Inspection Description - ELECTRIC - FINAL
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2000 | ELECTRIC - FINAL | Correction Required | ADDTL COMMS - RESCHEDULE INSP GEN CONTRACTOR TO BE HERE W/APPROVED PLANS 1. INSTALL DISCONNECTING MEANS AT WATER HEATER 2. INSTALL BOX EXTENSIONS AS REQD PER ART 370 NEC | |
| 04/26/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* | |
| 01/10/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* | |
| 01/07/2000 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
| 12/20/1999 | ELECTRIC - FINAL | Correction Required | ADDTL COMMS - 1. SEAL OPEN K.O AT SERVICE 2. LIGHTING DOESNT MEET LIGHT POLLUTION CODE NEED SHOE BOX TYPE FIXTURE WITH FLUSH LENSE 3. POUR ALL EYS FITTINGS PRIOR TO FINAL INSPECTION AND HAVE THIS CONTRACTOR ON SITE TO OPEN FITTINGS AND CLOSE AT INSPECTION 4. INSTALL BUSHINGS AS REQUIRED WHERE #4 OR LARGER PASSES THROUGH PANEL AND CONDUITS 5. FINISH WALKING COOLERS 6. GROUND GROUNDING BUSHING PER N.E.C. USING THE EQUIP GROUNDING CONDUCTOR IN THE CONDUIT UTILIZED | |
| 12/20/1999 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* |