Permit: T98CM04028

Parcel: 133146130

Inspection Status: Correction Required

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
10/14/1998 PLUMBING - ROUGH, SOIL Correction Required ADDTL COMMS - ALL JOINTS ON H2O LINES WERE TOO BE SOLDERED WITH SOLDER
10/13/1998 PLUMBING - ROUGH, SOIL Correction Required ADDTL COMMS - 1. AT TOILET TO SOIL LINE CHANGE SAN T TO A COMB FITTING. 2. AT LAV CHANGE COMB FITTING TO A WYE FITTING AND 1/8 BEND IF NEEDED. 3. BRING 2 VENT UP TO SAME HT AS LAV/ TOILET VENT. 4. NO SCREW FITTING UNDER GROUND
10/13/1998 PLUMBING - ROUGH, SOIL Not ready for Inspection NOT READY FOR INSPECTION
10/08/1998 PLUMBING - ROUGH, SOIL Correction Required ADDTL COMMS - 1. ANY JOINTS TO BE SILVER SOLDER TRY AND LIMIT THE NUMBERS OF JOINTS BY USING ROLLED COPPER TUBING. 2. SEE DIAGRAM FOR PLUMBING LEFT AS JOB- SITE USE SANITARY TEES TO CONNECT CLOSET BEND AND SHOWER TRAP. 3. DONT USE SAN TEES LAYING FLAT.
10/08/1998 PLUMBING - ROUGH, SOIL Denied DENIED