Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Correction Required
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 11/15/1999 |
ELECTRIC - CABLE DROP |
|
Correction Required |
ADDTL COMMS - 1) GROUND RODS CANNOT BE PLACED IN THE TRENCH UNLESS AN ATTEMPT HAS BEEN MADE TO DRIVE IN GROUND 2) GROUND WIRE EXPOSED MUST BE SECURED AND PROTECTED FROM PHYSICAL DAMAGE 3) RISER MUST EXTEND 12 BELOW GRADE |