Inspection Status: Correction Required
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 11/15/1999 |
ELECTRIC - CABLE DROP |
|
Correction Required |
ADDTL COMMS - 1) GROUND RODS CANNOT BE PLACED IN THE TRENCH UNLESS AN ATTEMPT HAS BEEN MADE TO DRIVE IN GROUND 2) GROUND WIRE EXPOSED MUST BE SECURED AND PROTECTED FROM PHYSICAL DAMAGE 3) RISER MUST EXTEND 12 BELOW GRADE |